Model |
BS-EX 20KS |
BS-EX 30KS |
BS-EX 40KS |
|
Input |
Supply voltage (V) |
3AV/N,400V,+15%/-25% (-15% to -30% at derating) |
|
Input Phases |
3 phase + N |
|
Nominal frequency |
50Hz/60Hz (selectable) |
|
Frequency tolerance (%) |
±10% |
|
Power factor @ nominal input voltage |
>0.95 |
|
Input current distortion (%) |
<8%standard, <5%option |
|
Inrush Peak current(A) |
1*1nom. |
|
Battery |
Battery nominal voltage |
288Vdc(26Ah*24pc) |
384Vdc(26Ah*32pc) |
384Vdc(26Ah*32pc standard,34Ah*32pc option) |
|
Minimum final discharge voltage |
252Vdc |
336Vdc |
336Vdc |
|
Max. charge current |
5A(standard), 10A(option) |
|
Static Voltage tolerance |
1% |
|
Output |
Rated apparent power(KVA) |
20KVA |
30KVA |
40KVA |
|
Rated active power(KW) |
16KW |
24KW |
32KW |
|
Output power Factor |
0.8 |
|
Overload:125%load |
10minutes(Ta:0~25 degree C); 5minutes(Ta:26~40degreeC) |
|
Overload:150%load |
60seconds(Ta:0~25degreeC); 30seconds(Ta:26~40degreeC) |
|
Output short-circuit |
300%load at 50Hz,10m sec; 150% load at 50Hz,5sec |
|
Output voltage rating |
3AC/N 400V, 380V or 415V parameterizable. (Default400Vac) |
|
Output frequency |
50Hz/60Hz |
|
Frequency tolerance: self-clocked: Line-clocked: |
0.1% ±0.1% (adjustable to±2%, 3% or 4%) |
|
Output voltage tolerance: Static |
±1% at balanced load. ±3%, at 50% unbalanced load.±4%, at 100% unbalanced load |
|
Dynamic |
±6.5% at 100% step. |
|
Output voltage distortion Linear full-load Non-linear full load |
<2% <8% |
|
Permissible non-linear load |
100% |
|
Load peak factor without derating |
3 |
|
UPS data |
AC/AC efficiency |
91%(Typical) |
|
Max. noise level@1 meter(dBA) |
≦54.6dBA |
≦56.7dBA |
|
EMC class |
EN62040-2(2006), Class C2 (Class C3 for Field Trial Units) |
|
Degree of protection |
IP21 |
|
Dimensions: H*W*D(mm) |
1400*500*822 |
1600*550*822 |
|
Net Weight(kg) (without battery inside UPS) |
113 |
184 |
187 |
|
Frame color (RAL scale) |
RAL scale 7016(dark gray) |
|
Cooling |
Forced (Built-in fan) |
|
Equipment mobility |
On casters |
|
Environmental |
Operating |
0~40 degree C |
|
Max. relative humidity at 20 degree. |
Acc. To EN 62040-3 |
|
Installation altitude: |
up to 1000m above sea level. |